Metronix SMART

Three Phase Whole Current Electronic Energy Meter with Anti Tamper Features

Connection3 Phase, 4 Wire
Accuracy ClassActive: 1.0 Reactive: 2.0
Operating Temperature-20°C to 60°C
Storage Temperature-25°C to 70°C
Humidity95 % RH
Dimension239.2mm x 117.6mm x 81.1mm
Metering TechnologyShunt and CT
Flame RetardationUL94-V
Lifetime10 Years (Min)
Weight1.82KG
Terminal BlockBS 5685 Standard
Voltage Range230V ± 20%
Starting Current0.4 % lb mA
Nomina; Current10(100) A
Power ConsumptionVoltage: < 1W, 4VA Current Circuit < 2VA[/av_cell][/av_row] [av_row row_style='' av_uid='av-7wquss'][av_cell col_style='' av_uid='av-24y8b2k']Power Factor[/av_cell][av_cell col_style='' av_uid='av-23nw524']Zero Lag - Zero Lead[/av_cell][/av_row] [av_row row_style='' av_uid='av-22cow7w'][av_cell col_style='' av_uid='av-20alpp8']Meter Constant[/av_cell][av_cell col_style='' av_uid='av-1xya3ak']200 imp/kWh, kVarh[/av_cell][/av_row] [av_row row_style='' av_uid='av-6srdt8'][av_cell col_style='' av_uid='av-1vpn54c']Frequency Range[/av_cell][av_cell col_style='' av_uid='av-1tbduzw']50 Hz ± 5%[/av_cell][/av_row] [av_row row_style='' av_uid='av-6bc0xo'][av_cell col_style='' av_uid='av-1pltov0']Impulse Voltage Rating[/av_cell][av_cell col_style='' av_uid='av-1o6pmks']12 kV[/av_cell][/av_row] [av_row row_style='' av_uid='av-1nhos0s'][av_cell col_style='' av_uid='av-1kuva7w']Energy Verification[/av_cell][av_cell col_style='' av_uid='av-1iuuovw']LED Pulse, Output Pulse Terminal[/av_cell][/av_row] [av_row row_style='' av_uid='av-1h5rm7w'][av_cell col_style='' av_uid='av-1fvy3i4']High Voltage Rating[/av_cell][av_cell col_style='' av_uid='av-1f212cs']4 kV[/av_cell][/av_row] [av_row row_style='' av_uid='av-1cqbip8'][av_cell col_style='' av_uid='av-1bqhfss']Surge Test[/av_cell][av_cell col_style='' av_uid='av-192hxng']4 kV[/av_cell][/av_row] [av_row row_style='' av_uid='av-4c3q4c'][av_cell col_style='' av_uid='av-15pgq30']Degree of Protection[/av_cell][av_cell col_style='' av_uid='av-14dih0s']IP54 of IEC 62059[/av_cell][/av_row] [av_row row_style='' av_uid='av-12pcmcc'][av_cell col_style='' av_uid='av-1101twc']External Magnetic Effect[/av_cell][av_cell col_style='' av_uid='av-zy6vjg']> 0.5 Tesla
MD Period30 / 60 Min
History Reading6 Month
Load Survey15 Min, 60 days
LCD Display9 Digital, IDS
LED Indication3 (Active, Reactive, Reverse)
ΤουMax 8 time zone / 6 tariff for energy and demand
  • Anti Tamper: Neutral Disturbance, Current Bypass, Current Reversal, Missing Neutral and Current Circuit Open
  • Punishment mechanism for external magnetic disturbance
  • Detection of missing potential, phase sequence reversal and AC/DC Magnetic (0.5 Tesla)
  • Measurement of kWh, kVarh, PF, Vrms, Irms and Maximum Demand, Event recording of tamper
  • Communication: Optical, RS232 and DLMS interface for meter reading
  • Multi-Tariff: TOD metering for kWh/kVarh and MD with 6 time zones programmable
  • History of billing readings for last six months
  • One point software calibration for improving production efficiency
  • Compliant with DLMS
  • IEC 62052-11:2003
  • IEC 62053-21: 2003
  • IEC 62053-23: 2003
  • BS 5685